Permit Number: T20CM00071
Parcel: 11617023A

Address:
610 N GRANDE AV

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T20CM00071
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2020 MARTIN BROWN FIRE REVIEW Approved
02/11/2020 IMONSHI1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: Taco Giro Enclose Porch
T20CM00071
Building Plan (2nd Review)

TRANSMITTAL DATE: February 11th, 2020

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. According to a previously approved site plan from 2000, the outside seating area with chairs and tables is labeled as a garden, not a dining area. Provide a previously approved (stamped by the PDSD) site plan that shows that area approved as dining area. Zoning will approve once this issue is resolved.

If you have any questions about this transmittal, please contact Iman Monshizadeh at Iman.Monshizadeh@tucsonaz.gov or by phone at 520-837-4082, or contact Steve.Shields@tucsonaz.gov or (520) 837-4956
02/18/2020 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a mechanical plan for the 2-mini split systems. Specify heating and cooling loads for determining the sizing of the new HVAC equipment. IECC C403.1.1.
2. Provide equipment specifications and performance ratings for the new mechanical equipment. IECC C403.3.2.
3. Specify how power will be brought to the new HVAC equipment. NEC 110.2.
02/18/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Passed
02/18/2020 RMCCOY1 WATER REVIEW Passed
02/18/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The addition is required to comply with the 2018 International Energy Conservation code. Please state how the new enclosed dining area will be made to comply with section C502.2 of the IECC for new construction; the addition alone is required to comply with the code. C502.2.
2. Keynote #6 states NEW DOOR, SEE WINDOW AND DOOR SCHEDULE; however, there is not door or window schedule included in the plans. IBC 107.2.1.
3. Provide construction details of the storefront window assembly attachment to the roof/ceiling and floor. IBC 107.2.1.
02/18/2020 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2020 ANY REJECT SHELF RECEIVED