Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T20CM00070
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/16/2020 | DRIVERA1 | ENGINEERING | REVIEW | Passed | |
| 01/16/2020 | DAVID RIVERA | NPPO | REVIEW | Passed | |
| 01/30/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T20CM00070 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. SECTIONS - DETAILS: 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. PLUMBING PLANS: 1. Provide a water heater spec sheet for verifying the capacity will sufficiently supply the building demand, P2801. Show a gas demand or electrical demand with appropriate energy supply. 2. Show the water pipe diameter between the meter and shut off valve in compliance with P2903.7. A minimum 1" service pipe is required for supplying water to more than 9.5 fixture units. ELECTRICAL PLANS: 1. Update the code reference to 2018 IRC. 2. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity. 3. Show receptacle outlets at each kitchen counter space wider than 12" with no point along the wall line more than 24" from a receptacle outlet, E3901.4.1. Show receptacles within 2' of counter edges or corners and no more than 4' apart. 4. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. GFCI protected, E3902.6. 5. Show a receptacle outlet within 3' of each lavatory basin in each bathroom, E3901.6. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4 and E3901.6. 6. Show one 20 AMP branch circuit in the laundry area; this circuit may not serve other locations, E3703.3 and 3901.8. 7. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |