Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T20CM00020
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2020 | NMARTEL1 | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: Nicholas Martell Planner PROJECT: T20CM00020 6731 S Promenade Pl Patio Addition TRANSMITTAL 01/02/2020 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The DDO process may only be used to reduce the driveway length to a carport, and not to a garage (UDC Section 3.11.1.B.4). In a developing area, the minimum driveway length to the edge of a sidewalk for a carport is nineteen (19) feet (UDC Section 6.4.5.C.2.b.1). The minimum driveway length for a carport is eighteen feet to the property line (UDC Section 6.4.5.C.2.b.1.a & b). The applicant is proposing a 2' setback to the rear of the property. The height of the wall is 8'. A 6' setback is required. DDO is required. |
| 01/02/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 02/11/2020 | PMARTIN1 | NPPO | REVIEW | Needs Review | |
| 02/11/2020 | PMARTIN1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review |