Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change NOTE: PROVIDE ALL CURRENT DRAWINGS WITH THE NEXT SUBMITTAL.

Comment not resolved. The suite is still nearly 1,000 CFM negative; show how the suite is to be balanced. Reference: Section 508.1, IMC 2018. [Third comment: Provide the dimensions for the makeup air ducts. Clarify the makeup air units - two are suggested on the roof plan but only one makeup air flow rate is given. Are the makeup air units heated, cooled, or evaporatively cooled? Based on the air flow rate data, the suite is nearly 1,000 CFM negative; show how the suite is to be balanced.] [Second comment: What is the design flow rate for the makeup air unit? Show the size and route of the supply ducts and the connections to the external supply plenum attached to the front of the hood. Explain the relevance of detail 4/A1.3 to this activity; are you planning to install an Accurex fan on a Greenheck curb?] [Initial comment: Provide adequate make-up air for the kitchen exhaust hood and provide specifications for the make-up air equipment and ductwork. Reference: Section 508.1 IMC 2018.]
05/19/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved. All fixtures shall be shown installed correctly and vented per one of the methods allowed in Chapter 9, IPC 2018. Quoting a section of the plumbing code is insufficient. [Third comment: Note: a floor sink may accommodate more than one indirect drain if it is properly sized (e.g. indirect drains from both P-6 and P-7 can discharge into a single floor sink).] [Second comment: Comment not addressed. P-6 is shown with direct connections.] [Initial comment: Provide separate indirect waste pipes for each compartment of P-6, the 3-compartment sink, to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018.]
2. Comment not resolved. Show the trench drains, their traps, and vents correctly installed and in proper relation to the building drain. Reference: Section 107.2.1, IBC 2018. [Third comment: Trench drains are a plumbing fixture, not a channel through which the building drains flow. Consult with a manufacturer's representative for installation instructions. All traps must be vented using one of the methods shown in Chapter 9, IPC 2018.] [Second comment: The specified trench drains are channels with outlets installed at an end cap or alongside the channel to which a trap is attached. Consult with a manufacturer's representative for installation instructions.] [Initial comment: Provide traps for the trench drains. Reference: Section1002.1, IPC 2018.]
3. Comment not resolved. Keynote #15 appears to show a two-way cleanout. Two-way cleanouts are only allowed to be used at the junction of a building drain and a building sewer. Reference: Section 708.1.8, IPC 2018. [Second comment: See Section 708, IPC 2018 for cleanout location information.] [Initial comment: Show the pipe sizes and cleanout locations on the revised waste riser diagram. Reference: Section 107.2.1, IBC 2018.]

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2020 ARUIZ1 OUT TO CUSTOMER Completed