Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM00002
Parcel: 10605003A

Address:
3901 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM00002
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Sheet A3.0 indicates that the millwork + counter storage has only 2901 square feet while the millwork + counter shop has 4077 square feet. Revise the ventilation calculations to include the shop area which is not best described as "shipping and receiving". The shop area is a special operation that is not described in Table 403.3.1.1, IMC 2018: an engineering analysis of the ventilation requirement will be needed. Reference: Section 403.1.1, IMC 2018.
2. The submitted data for the Duroair Silica Dust collector shows that it is employed with a modular and retractable enclosure, a Duroroom. The drawings do not show the size of the enclosure or show how dust or spray mists from the CNC, Stone Slab Router, Water System or the Slab Edge Polisher are to be collected. Provide an analysis of any necessary exhaust systems to collect dusts and spray mists from the equipment. Reference: Section 502.1, IMC 2018.
04/09/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The new plumbing plan indicates the water cutting system has a demand of 54 GPM and the waste water will be drained to a pump pit. Where will that water be sent and what impurities will be in the water?
04/17/2020 SARAH MEGGISON ZONING REVIEW Reqs Change Zoning Comment 1 from 3/10/2020 does not look as though it was addressed. Please include existing use and proposed use.
04/17/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/17/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 3; Sheet a0.1; Allowable Area Analysis: Please provide an allowable area analysis on this sheet following the IBC Section 508.4.2.
2. Previous Comment 3; Sheet a3.0; Travel Distance: Per the IBC Table 1017.2, the allowable travel distance is 250' for the sprinklered building. Please revise that sheet.
3. Sheet a3.0; Ground Floor Plan: A section cut through the Mercantile Storage area and the Mercantile area references 1/a7.0. Please revise that section reference.
4. General: Please provide written responses to all review comments.
04/17/2020 SARAH MEGGISON ZONING REVIEW Reqs Change Zoning Comment 1 from 3/10/2020 letter does not appear to have been addrssed. There are no use labels on sheet a1.0 on the site plan. Please make the changes and resubmit.