Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM00002
Parcel: 10605003A

Address:
3901 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM00002
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/23/2020 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a ventilation schedule for the new occupancy in accordance with IMC TABLE 403.3.1.1 to determine adequacy of the existing HVAC system for compliance with ventilation rates for the new occupancies. IMC 403.1.
2. Please provide a description of the equipment and fabrication process that will take place. Specify plumbing requirements for the water feature if needed, and provide a dust collection mechanical system which shows exhaust duct layout and termination point(s). Indicate distance from property lines and public ways. Indicate make-up air requirements for equipment exhaust systems. IMC 106.4.1.
01/23/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the panel schedule for new panel L3; show all connected loads and electrical load calculations to the panel. NEC 110.3
2. Provide grounding details of the GEC and bonding details of the gutter, building steel, water pipe and gas piping. Specify the sizes of all grounds, bonding conductors and jumpers. NEC 250.4
3. Electrical equipment that requires examination, adjustment, servicing or maintenance while energized shall be field or factory marked to warn of potential electrical flash hazards. NEC 110.16.
01/23/2020 MARTIN BROWN FIRE REVIEW Reqs Change 1. Occupant load. The OLF of 200 is used for determining the occupant load of the fabrication area. Per IBC TABLE 1004.5 this is the occupant load factor used for Group H-5 fabrication and manufacturing areas. If Group H-5 occupancy exists please provide code analysis and locate on the floor plan. IBC TABLE 1004.5.
2. On the building code text box, please change the 2011 National Electric Code to the 2017 NEC; remove 'Pima County, Arizona municipal code' and replace with City of Tucson adopted codes and amendments; and add ICC A117.1-2009 Accessible and Usable Buildings and Facilities.
3. Please provide a code analysis of the building for the new occupancy classification; include an allowable area analysis, designation of separated or non-separated occupancies and and maximum travel distances. IBC 107.2.1.
4. Please indicate the travel distances within the exit access portion of the egress system. Show measurements from occupied portions of the building to an EXIT. Show the travel distance from the most remote occupied space on the second floor to an EXIT. IBC 1017.1.
01/23/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Occupant load. The OLF of 200 is used for determining the occupant load of the fabrication area. Per IBC TABLE 1004.5 this is the occupant load factor used for Group H-5 fabrication and manufacturing areas. If Group H-5 occupancy exists please provide code analysis and locate on the floor plan. IBC TABLE 1004.5.
2. On the building code text box, please change the 2011 National Electric Code to the 2017 NEC; remove 'Pima County, Arizona municipal code' and replace with City of Tucson adopted codes and amendments; and add ICC A117.1-2009 Accessible and Usable Buildings and Facilities.
3. Please provide a code analysis of the building for the new occupancy classification; include an allowable area analysis, designation of separated or non-separated occupancies and and maximum travel distances. IBC 107.2.1.
4. Please indicate the travel distances within the exit access portion of the egress system. Show measurements from occupied portions of the building to an EXIT. Show the travel distance from the most remote occupied space on the second floor to an EXIT. IBC 1017.1.
5. Provide structural plans and framing details for new door openings; indicate size, frame and hardware specifications for all new doors; provide a door schedule with references to door tags. Label doors as new or existing. IBC 107.2.1.
6.Provide wall sections and framing details for all new walls and/or partitions. Specify construction materials and methods of fastening at the floor and ceiling levels. IBC 107.2.1.
7. Verify that new materials used for new construction is in compliance with the materials approved for use in Type II buildings. IBC 603.1
8. Item #3 of the general floor plan stipulates that rated fire assemblies are to be provided. The responsibility for determining required fire rated assemblies is with the design professional. If any items of the general notes do not pertain to this project, please remove from the plans. IBC 107.2.1.
9. Show the location of the 1 hr. fire separation (horizontal) on the plans; if not applicable please remove from the legend. IBC 107.2.1.
10. Please submit a reflective ceiling plan; show locations of all EXIT signs. Label new and existing lighting fixtures. IBC 107.2.
11. Please provide a description of the geometric non-labeled circle, rectangle and enclosure around the GMM station. IBC 107.2.1.
12.Please explain '25 foot allowed use encroachment' description on the floor plan. If it refers to zoning please locate this on a zoning specific floor plan and not on the construction floor plans. IBC 107.2.1.
13. On the floor plan, label all new and existing doors. Provide a door schedule that shows door type, framing details and hardware specifications. IBC 1010.1.9.4.
14. The layout and description of equipment on electrical plan ep101 is different from the layout and description of equipment shown on floor plan a3.0. Please coordinate architectural and electrical plans for type and layout of equipment. IBC 107.2.1.
01/23/2020 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Passed
01/27/2020 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T20CM00002 - Int. Demo and Tenant Improvement
Building Plan Review (1st Review) Tucson Stoneworks
3901 N. Oracle Road - C-2 / I-1 Zoning

TRANSMITTAL DATE: January 27, 2020

DUE DATE: February 5. 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for interior demo and tenant improvement for compliance with UDC requirements. Label the proposed principal use of the building i.e.; Retail sales, manufacturing, commercial storage. Keep in mind that for zoning the principal use is what zoning uses for review of the proposal.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning compliance based on the principal use.

Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning comments are addressed, the building plans can be approved by zoning.

3. COMMENT: Additional comments may be forthcoming on the next review based on the proposed principal use and possible use specific standards.


If you have any questions about this transmittal, Contact David Rivera on Tuesday, Wednesday or Thursday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
01/27/2020 DAVID RIVERA ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: TUCSONstoneworks
T20CM00002
Building Plan (1st Review)

TRANSMITTAL DATE: January 3, 2020

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Demonstrate that this site complies with UDC Article 4.9.4.C.9.

3. Based on sheet ep101 and the layout of equipment it appears that the proposed "Industrial Area 1,691 SF" is much larger than the square footage listed on the plan, clarfy.

4. The parking and bicycle calculations is not correct. Either remove the calc from the plan as it is not need or the calc should be based on the primary use only.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/28/2020 SSHIELD1 ENGINEERING REVIEW Passed
04/07/2020 RMCCOY1 WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2020 SBORZAK1 REJECT SHELF Completed