Permit Number: T20CM00002
Parcel: 10605003A

Address:
3901 N ORACLE RD

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T20CM00002
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: TUCSONstoneworks
T20CM00002
Building Plan (1st Review)

TRANSMITTAL DATE: January 3, 2020

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Demonstrate that this site complies with UDC Article 4.9.4.C.9.

3. Based on sheet ep101 and the layout of equipment it appears that the proposed "Industrial Area 1,691 SF" is much larger than the square footage listed on the plan, clarfy.

4. The parking and bicycle calculations is not correct. Either remove the calc from the plan as it is not need or the calc should be based on the primary use only.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/03/2020 ENEWCOM1 ADA REVIEW Passed
01/03/2020 SSHIELD1 ENGINEERING REVIEW Passed
01/03/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/06/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
01/06/2020 ENEWCOM1 FIRE REVIEW Needs Review
01/07/2020 SBORZAK1 WWM REVIEW Completed