Permit Number: T20BU00503
Parcel: 12514010A

Address:
3130 E 4TH ST

Review Status: Completed

Review Details: WALLS

Permit Number - T20BU00503
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2021 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T20BU00503
Site Wall – T20DV06149 (1st Review)
3130 E 4th St.

TRANSMITTAL DATE: 01/11/2021

DUE DATE: 12/10/2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Provide the existing wall height and the total proposed wall height (existing height + proposed addition height). The maximum allowed height of a solid site wall is 6’. The wall can be 10’ if at least 75% of the area above six feet in height is left unobstructed and open through the use of architectural elements, such as arches, columns, or wrought iron.

If the wall exceeds 10’ a Design Development Option (DDO) must be pursued. For DDO requirements see: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf


If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
11/25/2020 ANDREW CONNOR NPPO REVIEW Passed
12/01/2020 SBLOOD1 ENGINEERING REVIEW Passed
12/09/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Passed