Permit Number: T20BU00498
Parcel: 12513068B

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T20BU00498
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2020 STEVE SHIELDS ZONING REVIEW Passed
10/30/2020 SSHIELD1 ENGINEERING REVIEW Passed
11/02/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/02/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/02/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise General Note #1 on sheet SP-1. Pool backwash shall be discharged to the sanitary sewer system, not to the storm drain. Reference: Pima County Procedure PN0027-01, 7/1/2017
11/16/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved