Permit Number: T20BU00051
Parcel: 134244300

Address:
6363 E 22ND ST

Review Status: Active

Review Details: RESUBMITTAL

Permit Number - T20BU00051
Review Name: RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change It does not appear any of the first review comments were addressed and revised as required.
1. The adopted edition of the codes by the City of Tucson are as follows; 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2018 International Energy Conservation Code, 2018 International Swimming Pool & Spa Code, 2017 National Electric Code, Arizona Administrative Code Title 18 Chapter 5 for public and semi-public swimming pools, and ICC A117.1-2009 Accessible and Usable Buildings and Facilities. Please list these adopted codes on the CODES textbox.
2. Indicate the building code classification and occupant loads for the pool, spa and enclosure area. Provide a project summary and code evaluation for the area containing the pool, spa and mechanical room. IBC 302.1, IBC TABLE 1004.5.
3. Indicate and verify compliance with the Arizona Administrative Code Sec. 18-5-208 for the pool and spa construction.
4. Provide structural calculations and drawings for the pool and spa design. Indicate the distance from the pool to adjacent walls and structures. IBC 107.2.1.
5. Submit a soils report per references listed in the STRUCTURAL NOTES. This is required for the structural review of the pool. IBC 107.2.1.
6. Provide a DOOR and WINDOW SCHEDULE of all ingress and egress openings into the pool and spa enclosure. Specify hardware, glazing and framing details. IBC 107.2.1.
05/22/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change No response or compliance with the previous electrical plan review comments.