Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20BU00051
Parcel: 134244300

Address:
6363 E 22ND ST

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T20BU00051
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The adopted edition of the codes by the City of Tucson are as follows; 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2018 International Energy Conservation Code, 2018 International Swimming Pool & Spa Code, 2017 National Electric Code, Arizona Administrative Code Title 18 Chapter 5 for public and semi-public swimming pools, and ICC A117.1-2009 Accessible and Usable Buildings and Facilities. Please list these adopted codes on the CODES textbox.
2. Indicate the building code classification and occupant loads for the pool, spa and enclosure area. Provide a project summary and code evaluation for the area containing the pool, spa and mechanical room. IBC 302.1, IBC TABLE 1004.5.
3. Indicate and verify compliance with the Arizona Administrative Code Sec. 18-5-208 for the pool and spa construction.
4. Provide structural calculations and drawings for the pool and spa design. Indicate the distance from the pool to adjacent walls and structures. IBC 107.2.1.
5. Submit a soils report per references listed in the STRUCTURAL NOTES. This is required for the structural review of the pool. IBC 107.2.1.
6. Provide a DOOR and WINDOW SCHEDULE of all ingress and egress openings into the pool and spa enclosure. Specify hardware, glazing and framing details. IBC 107.2.1.
02/25/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Provide electrical plans for the pool, spa and all associated equipment. Specify grounding and bonding to all pool equipment, metal within 5' from the pool, metal ladders, metal handrails and equipotential bond. NEC 680.26.
2. Show all lighting and receptacle locations in the pool/spa enclosure and specify vertical and horizontal clearances to water's edge. NEC 680.22.
3. Show all branch circuit wiring and feeders; specify conductor sizes and types, raceway size and type and overcurrent protection with panel schedules. NEC 680.23(F)(1).
4. Specify wiring methods for all branch-circuit wiring and feeders on the supply side of enclosures and junction boxes to conduits installed in corrosive environments where pool supplies are used and sored. NEC 680.23(F)(1).
03/06/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/06/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2020 ARUIZ1 APPROVAL SHELF Completed
05/05/2020 ARUIZ1 OUT TO CUSTOMER Completed
05/05/2020 ARUIZ1 REJECT SHELF Completed