Permit Number: T20BU00014
Parcel: 11704214A

Address:
58 E 5TH ST

Review Status: Completed

Review Details: WALLS

Permit Number - T20BU00014
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2020 ANDREW CONNOR NPPO REVIEW Passed
01/27/2020 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T20BU00014 - New Fence on top of parking structure wall
Building Plan Review (1st Review) 7th Avenue Commons
58 E. 5th Street - C-3 Zoning

TRANSMITTAL DATE: January 27, 2020

DUE DATE: February 5. 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the plans for the proposed fencing but cannot approve them at this time. Please address the following comments and resubmit the plans with corrections made as required and include any additional documentation that may be required by staff for and IID approval.

The existing development was reviewed under the Infill Incentive District special application review and approval process. The proposal should be reviewed by staff for compliance with the IID approval. Contact Maria Gayosso at 520-837-6972 or Nick Ross 520-837-4029 for information related to an IID review.

2. COMMENT: Label the street names Stone Avenue and 5th Street that are adjacent to the subject site.

3. COMMENT: Label the zoning of the property as a general note.

If an IID review and approval is required, list the IID case number, date f approval and conditions if any.

If you have any questions about this transmittal, Contact David Rivera on Tuesday, Wednesday or Thursday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
01/31/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change 1) Refer to zoning comments. A seperate development package submittal and approval is required prior to approval of the building plans
01/31/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Construction plans are required to be sealed by a professional registrant. AZ Statute 32-144.
2. Provide elevation views of the new fence and specify materials, framing members and attachment to deck. IBC 107.2.1.
3. Provide details of the attachment and fasteners for attaching the fence to the deck. IBC 107.2.1.
4. If the new fence is also required to constructed as a guard in accordance with IBC 1015.2 it will have to meet a horizontal 50 lbs. per linear foot. IBC 1607.8.