Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - RE-SUBMITTAL
Permit Number - T19RW04070
Review Name: ROW SWF - RE-SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/12/2019 | JSANDER1 | START | START | Completed | |
08/27/2019 | CSALTZM1 | DOT ENGINEERING | REVIEW | Approved | |
08/29/2019 | JSANDER1 | REAL_ESTATE | REVIEW | Approved | COT License# LF1087 |