Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - RE-SUBMITTAL
Permit Number - T19RW03981
Review Name: ROW SWF - RE-SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/30/2020 | JSANDER1 | START | START | Completed | |
05/01/2020 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom |
05/04/2020 | RICHARD LEIGH | DOT ENGINEERING | REVIEW | Reqs Change | 1. Revise temporary traffic control plan to include a pedestrian detour route. 2. Add the following notes to Small Cell Plan. - Contractor shall repair all landscaping disturbed. This includes irrigation, plantings, groundcover, and hardscape. - All concrete damaged or removed shall be replaced as a whole to the nearest joint. - Stormwater Good housekeeping measures shall be practiced during work and construction. - Midvale Road is under a pavement cut moratorium until September 13, 2023. Pavement cuts within Midvale Road will require prior approval from the City of Tucson, Department of Transportation and Mobility. |
05/04/2020 | JSANDER1 | DOT_WATER | REVIEW | Approved |