Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - SUBMITTAL
Permit Number - T19RW03848
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/10/2019 | JSANDER1 | START | START | Completed | |
07/10/2019 | JSANDER1 | HISTORIC | Review | Needs Review | RECOMMENDATION: Approval with Conditions Condition(s): Archaeological monitoring required. Plan must be submitted to HPO for approvial prior to obtaining a permit. |
07/22/2019 | LINZUNZA | IT_NETWK | REVIEW | Approved | |
07/26/2019 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does not have any comments or concerns at this time. Paul Rosenboom |
07/26/2019 | JSANDER1 | DOT_ELEC | REVIEW | Reqs Change | Add note to include luminaire requirement for "ATBM P10 MVOLT R2 3K MP NL P7", with ATBMHSS House Side Shield, and Intermatic EK4536 Photo Control. |
07/29/2019 | JSANDER1 | REAL_ESTATE | REVIEW | Needs Review | |
07/30/2019 | CSALTZM1 | DOT ENGINEERING | REVIEW | Denied | 1) Place new pole and meter pedestal behind five ft. wide future ADA sidewalk. Pole and meter pedestal shall have a minimum one ft. space from back edge of sidewalk. For design of location of future five ft. sidewalk place directly behind curb. |
07/30/2019 | CSALTZM1 | WATER | WATER | Approved |