Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - SUBMITTAL
Permit Number - T19RW03376
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2019 | LINZUNZA | START | START | Completed | |
06/14/2019 | LINZUNZA | HISTORIC | Review | Approved | RECOMMENDATION: Approval |
06/17/2019 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does not have any comments or concerns at this location. Paul Rosenboom |
06/18/2019 | RLEIGH1 | WATER | REVIEW | Approved | |
06/18/2019 | RICHARD LEIGH | DOT ENGINEERING | REVIEW | Approved | |
06/19/2019 | LINZUNZA | IT_NETWK | REVIEW | Approved | |
06/20/2019 | JSANDER1 | DOT_ELEC | REVIEW | Reqs Change | 1. Add note to include luminaire requirement for "ATBM P10 MVOLT R2 3K MP NL P7", with ATBMHSS House Side Shield, and Intermatic EK4536 Photo Control. 2. Add note: "a 25 FT coil of #4 Bare copper will be placed in the foundation prior to the concrete pour, and attached to the pole at the grounding lug". 3. On sheet G-2 detail #2 show correct bussmans fuse holders and the correct fuses LP-CC-5 to be used. |
06/20/2019 | JSANDER1 | REAL_ESTATE | REVIEW | Needs Review |