Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2019 LINZUNZA START START Completed
06/14/2019 LINZUNZA HISTORIC Review Approved RECOMMENDATION: Approval
06/17/2019 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns at this location. Paul Rosenboom
06/18/2019 RLEIGH1 WATER REVIEW Approved
06/18/2019 RICHARD LEIGH DOT ENGINEERING REVIEW Approved
06/19/2019 LINZUNZA IT_NETWK REVIEW Approved
06/20/2019 JSANDER1 DOT_ELEC REVIEW Reqs Change 1. Add note to include luminaire requirement for "ATBM P10 MVOLT R2 3K MP NL P7", with ATBMHSS House Side Shield, and Intermatic EK4536 Photo Control.
2. Add note: "a 25 FT coil of #4 Bare copper will be placed in the foundation prior to the concrete pour, and attached to the pole at the grounding lug".
3. On sheet G-2 detail #2 show correct bussmans fuse holders and the correct fuses LP-CC-5 to be used.
06/20/2019 JSANDER1 REAL_ESTATE REVIEW Needs Review