Permit Number: T19RW03375
Parcel: 999999999

Address:
5211 S PARK AV

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T19RW03375
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2019 LINZUNZA START START Completed
06/14/2019 LINZUNZA HISTORIC Review Approved RECOMMENDATION: Approval
06/17/2019 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns at this location. Paul Rosenboom
06/18/2019 RLEIGH1 WATER REVIEW Approved
06/18/2019 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change Reviewer:

Richard Leigh
520-837-6647
Richard.Leigh@tucsonaz.gov

Site Plan

1) Revise drawing to depict sight visibility triangle, pursuant to City of Tucson Technical Standards Section 10-01.5.0, for the driveway south of the site. The power meter must be located outside of the sight triangle.
06/19/2019 LINZUNZA IT_NETWK REVIEW Approved
06/21/2019 JSANDER1 DOT_ELEC REVIEW Reqs Change Add in notes for;
1) The correct wire for the street light #12 THW/XHHW
2) "a 25 FT coil of #4 Bare copper will be placed in the foundation prior to the concrete pour, and attached to the pole at the grounding lug".
3) Bussmans HEB-AA fuse holders and LP-CC-5 fuses for the street light
4) Should existing City of Tucson pull box be damaged during construction, it shall be replaced with:
"Pull box(s) shall be Christy brand "Old Castle precast, FIBERLYTE 10" x 17" model FL09T, with medium duty cover". Cover shall have etched marking designating "streetlights" in accordance with PAG Specifications section 732-2.03 and details T-101 (3) for cover lettering".
For a #5 pull box in above substitute (Fiberlyte 13" x 24" model FL30T) etc.
06/21/2019 JSANDER1 REAL_ESTATE REVIEW Needs Review