Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - SUBMITTAL
Permit Number - T19RW02924
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/24/2019 | LINZUNZA | START | START | Completed | |
05/24/2019 | LINZUNZA | HISTORIC | Review | Approved | RECOMMENDATION: Approval |
05/28/2019 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does run paralell to 6th Av. on both east and west roadside. The contractor would be responsible for any damages or rerouting of irrigation lines. The contractor shall be responsible to install sleeves through concrete or any other hardscaped surface. Field meet with TDOT Street maintenance. |
05/30/2019 | LINZUNZA | IT_NETWK | REVIEW | Approved | |
06/07/2019 | JSANDER1 | DOT_ELEC | REVIEW | Approved | The following review comments have been addressed in revised plan: Sheet G1, N.T.S. 5 of this plan set needs to look like the one from the plan set for 501 N Riverside. Sheet S1 - 1. It appears the luminaire mounting height lost 7 FT, not specified, Luminiare shall be mounted at 35 FT AGL, on a 20 FT long mast arm. |
06/13/2019 | CSALTZM1 | DOT ENGINEERING | REVIEW | Approved | |
06/13/2019 | JSANDER1 | REAL_ESTATE | REVIEW | Approved | COT License# LF1022 |
06/13/2019 | CSALTZM1 | WATER | REVIEW | Approved |