Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - SUBMITTAL
Permit Number - T19RW02865
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/22/2019 | LINZUNZA | START | START | Completed | |
05/22/2019 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does not have any comments or concerns at this location. |
05/22/2019 | LINZUNZA | HISTORIC | Review | Approved | RECOMMENDATION: Approval |
05/23/2019 | LINZUNZA | IT_NETWK | REVIEW | Approved | |
06/11/2019 | CSALTZM1 | DOT ENGINEERING | REVIEW | Denied | 1) Move pole,pull box and meter pedestal adjacent to property line. Placing pole close to property line will acommondate future ADA sidewalk without second relocation of pole. |
06/11/2019 | JSANDER1 | DOT_ELEC | REVIEW | Reqs Change | The DOT_ELEC reviewer requires: 1. Note to include luminaire requirement for "ATBM P10 MVOLT R2 3K MP NL P7", and Intermatic EK4536 Photo Control.2. Note to include "Pull box(s) shall be Christy brand "Old Castle precast, FIBERLYTE 10" x 17" model FL09T, with medium duty cover". Cover shall have etched marking designating "streetlights" in accordance with PAG Specifications section 732-2.03 and details T-101 (3) for cover lettering". For a #5 pull box in above substitute (Fiberlyte 13" x 24" model FL30T) etc. |
06/11/2019 | CSALTZM1 | WATER | REVIEW | Approved | |
06/12/2019 | JSANDER1 | REAL_ESTATE | REVIEW | Needs Review |