1140 E GANLEY RD

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T19RW02734
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2019 JSANDER1 START START Completed
05/15/2019 JSANDER1 HISTORIC Review Denied Insufficient Information.
Cultural Resources survey required.
Please resubmit with a cultural resources survey report of the project site that meets Arizona State Museum standards. - per Allison Diehl
05/16/2019 LINZUNZA IT_NETWK REVIEW Approved
05/16/2019 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns at this location.
05/17/2019 ROBERT SHERRY WATER REVIEW Passed
05/20/2019 JSANDER1 DOT_ELEC REVIEW Reqs Change 1. sheet G2 plan 2 nothing in place for the HEB-AA Bussmans fuse holders and the LP-CC-5 fuses for the light. 2. Appropriate Christy pullbox:"Pull box(s) shall be Christy brand "Old Castle precast, FIBERLYTE 10" x 17" model FL09T, with medium duty cover". Cover shall have etched marking designating "streetlights" in accordance with PAG Specifications section 732-2.03 and details T-101 (3) for cover lettering".For a #5 pull box in above substitute (Fiberlyte 13" x 24" model FL30T) etc.
3. A 25' COIL #4 BARE COPPER CONDUCTOR SHALL BE INSTALLED IN THE FOUNDATION BEFORE THE CONCRETE IS POURED AND TO BE CONNECTED TO THE GROUNDING
06/11/2019 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change Reviwer:

Richard Leigh
520-837-6647
richard.leigh@tucsonaz.gov

1) Revise drawing to relocate pole, power meter and vaults closer to property line to provide space for future sidewalk. The face of the pole and power meter should be no closer than 7.5' from face of curb.
06/12/2019 JSANDER1 REAL_ESTATE REVIEW Needs Review