Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19RW02732
Parcel: 999999999

Address:
2350 E BILBY RD

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T19RW02732
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2019 LINZUNZA START START Completed
05/15/2019 CSALTZM1 WATER REVIEW Approved
05/15/2019 CSALTZM1 DOT ENGINEERING REVIEW Approved
05/15/2019 LINZUNZA HISTORIC Review Approved RECOMMENDATION: Approval
05/16/2019 LINZUNZA IT_NETWK REVIEW Approved
05/16/2019 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does run within the right of way. If Transportation irrigation lines are in the way, the contractor shall reroute, sleeve if going through or under concreate or driveways. Any and all repairs and modifications shall be done at the contractor's expense and by a landscape irrigation company.
05/20/2019 JSANDER1 DOT_ELEC REVIEW Reqs Change Plans need to provide:
1. A 25' COIL #4 BARE COPPER CONDUCTOR SHALL BE INSTALLED IN THE FOUNDATION BEFORE THE CONCRETE IS POURED AND TO BE CONNECTED TO THE GROUNDING SCREW AT THE HAND HOLE AFTER PLACING THE POLE.
2. HEB-AA Bussman's fuse holders or the LP-CC-5 fuses for the City light
3. "Pull box(s) shall be Christy brand "Old Castle precast, FIBERLYTE 10" x 17" model FL09T, with medium duty cover". Cover shall have etched marking designating "streetlights" in accordance with PAG Specifications section 732-2.03 and details T-101 (3) for cover lettering".For a #5 pull box in above substitute (Fiberlyte 13" x 24" model FL30T) etc.
05/20/2019 JSANDER1 REAL_ESTATE REVIEW Needs Review