Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - SUBMITTAL
Permit Number - T19RW02732
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/15/2019 | LINZUNZA | START | START | Completed | |
05/15/2019 | CSALTZM1 | WATER | REVIEW | Approved | |
05/15/2019 | CSALTZM1 | DOT ENGINEERING | REVIEW | Approved | |
05/15/2019 | LINZUNZA | HISTORIC | Review | Approved | RECOMMENDATION: Approval |
05/16/2019 | LINZUNZA | IT_NETWK | REVIEW | Approved | |
05/16/2019 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does run within the right of way. If Transportation irrigation lines are in the way, the contractor shall reroute, sleeve if going through or under concreate or driveways. Any and all repairs and modifications shall be done at the contractor's expense and by a landscape irrigation company. |
05/20/2019 | JSANDER1 | DOT_ELEC | REVIEW | Reqs Change | Plans need to provide: 1. A 25' COIL #4 BARE COPPER CONDUCTOR SHALL BE INSTALLED IN THE FOUNDATION BEFORE THE CONCRETE IS POURED AND TO BE CONNECTED TO THE GROUNDING SCREW AT THE HAND HOLE AFTER PLACING THE POLE. 2. HEB-AA Bussman's fuse holders or the LP-CC-5 fuses for the City light 3. "Pull box(s) shall be Christy brand "Old Castle precast, FIBERLYTE 10" x 17" model FL09T, with medium duty cover". Cover shall have etched marking designating "streetlights" in accordance with PAG Specifications section 732-2.03 and details T-101 (3) for cover lettering".For a #5 pull box in above substitute (Fiberlyte 13" x 24" model FL30T) etc. |
05/20/2019 | JSANDER1 | REAL_ESTATE | REVIEW | Needs Review |