Permit Number: T19RW02728
Parcel: 999999999

Address:
6146 S DUNTON AV

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T19RW02728
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2019 LINZUNZA START START Completed
05/15/2019 CSALTZM1 WATER REVIEW Approved
05/15/2019 CSALTZM1 DOT ENGINEERING REVIEW Denied 1) Place pole behind future Sidewalk. Use a five foot wide sidewalk. Between back of sidewalk and pole/ meter pedestal use a one foot.
05/15/2019 LINZUNZA HISTORIC Review Approved RECOMMENDATION: Approval
05/16/2019 LINZUNZA IT_NETWK REVIEW Approved
05/16/2019 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns.
05/20/2019 JSANDER1 DOT_ELEC REVIEW Reqs Change 1. sheet G2 plan 2 nothing in place for the HEB-AA Bussmans fuse holders and the LP-CC-5 fuses for the light.
2. Appropriate Christy pullbox:"Pull box(s) shall be Christy brand "Old Castle precast, FIBERLYTE 10" x 17" model FL09T, with medium duty cover". Cover shall have etched marking designating "streetlights" in accordance with PAG Specifications section 732-2.03 and details T-101 (3) for cover lettering".For a #5 pull box in above substitute (Fiberlyte 13" x 24" model FL30T) etc.
3. A 25' COIL #4 BARE COPPER CONDUCTOR SHALL BE INSTALLED IN THE FOUNDATION BEFORE THE CONCRETE IS POURED AND TO BE CONNECTED TO THE GROUNDING SCREW AT THE HAND HOLE AFTER PLACING THE POLE.
05/20/2019 JSANDER1 REAL_ESTATE REVIEW Needs Review