Permit Number: T19RW02727
Parcel: 999999999

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T19RW02727
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2019 JSANDER1 START START Completed
05/15/2019 JSANDER1 HISTORIC Review Denied RECOMMENDATION: Insufficient Information
Cultural Resources survey required.
Please resubmit with a cultural resources survey report of the project site that meets Arizona State Museum standards.
05/16/2019 LINZUNZA IT_NETWK REVIEW Approved
05/16/2019 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comment or concerns.
05/17/2019 ROBERT SHERRY WATER REVIEW Passed
05/20/2019 JSANDER1 DOT_ELEC REVIEW Reqs Change Plans need to provide:
1. sheet G2 plan 2 nothing in place for the HEB-AA Bussmans fuse holders and the LP-CC-5 fuses for the light.
2. Appropriate Christy pullbox:
"Pull box(s) shall be Christy brand "Old Castle precast, FIBERLYTE 10" x 17" model FL09T, with medium duty cover". Cover shall have etched marking designating "streetlights" in accordance with PAG Specifications section 732-2.03 and details T-101 (3) for cover lettering".
For a #5 pull box in above substitute (Fiberlyte 13" x 24" model FL30T) etc.
06/11/2019 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change Reviewer:
Richard Leigh
520-837-6647
Richard.leigh@tucsonaz.gov


1) Revise drawing to relocate pole, power meter and vaults as close as possible to property line and to allow room for the mobile home on the adjacent property to be moved. Post barricades may be considered for protection of the meter and pole.
06/12/2019 JSANDER1 REAL_ESTATE REVIEW Needs Review