Permit Number: T19RW02700
Parcel: 999999999

Address:
1220 W DREXEL RD

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T19RW02700
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2019 LINZUNZA START START Completed
05/22/2019 LINZUNZA HISTORIC Review Needs Review Condition(s): Archaelogical monitoring required. Plan must be submitted to HPO for approval prior to obtaining a permit.
05/23/2019 LINZUNZA IT_NETWK REVIEW Approved
05/24/2019 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns at this location.
06/05/2019 JSANDER1 DOT_ELEC REVIEW Reqs Change Add notes:
1. Light on pole will have a 30' mounting height for the light fixture (+or- a few inches may be acceptable) with an 8' or 10' mast arm.
2. calling out the ATBM P10 MVOLT R2 3K MP NL P7 Autobahn , Photo Control Brand: Intermatic Model:LED4536SC voltage operating range 120 volts to 277 volts; shield not required.
3. Pull box(s) shall be Christy brand "Old Castle precast, FIBERLYTE 10" x 17" model FL09T, with medium duty cover". Cover shall have etched marking designating "streetlights" in accordance with PAG Specifications section 732-2.03 and details T-101 (3) for cover lettering.
06/11/2019 CSALTZM1 DOT ENGINEERING REVIEW Approved
06/11/2019 CSALTZM1 WATER REVIEW Approved
06/12/2019 JSANDER1 REAL_ESTATE REVIEW Needs Review