Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - SUBMITTAL
Permit Number - T19RW02700
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/22/2019 | LINZUNZA | START | START | Completed | |
05/22/2019 | LINZUNZA | HISTORIC | Review | Needs Review | Condition(s): Archaelogical monitoring required. Plan must be submitted to HPO for approval prior to obtaining a permit. |
05/23/2019 | LINZUNZA | IT_NETWK | REVIEW | Approved | |
05/24/2019 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does not have any comments or concerns at this location. |
06/05/2019 | JSANDER1 | DOT_ELEC | REVIEW | Reqs Change | Add notes: 1. Light on pole will have a 30' mounting height for the light fixture (+or- a few inches may be acceptable) with an 8' or 10' mast arm. 2. calling out the ATBM P10 MVOLT R2 3K MP NL P7 Autobahn , Photo Control Brand: Intermatic Model:LED4536SC voltage operating range 120 volts to 277 volts; shield not required. 3. Pull box(s) shall be Christy brand "Old Castle precast, FIBERLYTE 10" x 17" model FL09T, with medium duty cover". Cover shall have etched marking designating "streetlights" in accordance with PAG Specifications section 732-2.03 and details T-101 (3) for cover lettering. |
06/11/2019 | CSALTZM1 | DOT ENGINEERING | REVIEW | Approved | |
06/11/2019 | CSALTZM1 | WATER | REVIEW | Approved | |
06/12/2019 | JSANDER1 | REAL_ESTATE | REVIEW | Needs Review |