Review Details: ROW SWF - SUBMITTAL

Permit Number - T19RW01394
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2019 LINZUNZA START START Completed
03/22/2019 LINZUNZA IT_NETWK REVIEW Approved
03/22/2019 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved TDOT Streets irrigation does not have any conflicts at this location.
03/22/2019 LINZUNZA HISTORIC Review Approved Approval with conditions - Archaeological monitoring required. Plan must be submitted for HPO approval.
The proposed pole locations is within a City of Tucson Archaeological Sensitivit Zone and within the recorded boundaries of AZ BB:13:784 (ASM). This site has yielded signifcan archaeological deposits associated with Historic Block 208. Archaeological monitoring is required for all ground disturbance. A monitoring and discovery plan must be submitted to HPO for approval prior to the start of work, and results of monitoring sent to the City of Tucson HPO and the Arizona State Museum.
04/08/2019 JSANDER1 DOT_ELEC REVIEW Reqs Change 1. Sheet E1 to call out specific pull box used by City of Tucson: Christy
2. Revise for Power Sharing
3. Add note about where to take old pole for salvage
4. new pole should match color of poles in the area and that contractor needs to paint any exposed wires to match color of the pole and seal any open handholes for safety from bee's, water, and bird nesting.
04/12/2019 CSALTZM1 DOT ENGINEERING REVIEW Approved
04/12/2019 ROBERT SHERRY WATER REVIEW Passed
04/25/2019 JSANDER1 REAL_ESTATE REVIEW Approved COT License#: LF998