Permit Number: T19RW01203
Parcel: 999999999

Address:
5990 S TUCSON BL

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T19RW01203
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2019 JSANDER1 START START Completed
03/06/2019 JSANDER1 HISTORIC Review Approved Approved per Allison Diehl.
03/14/2019 RLEIGH1 WATER REVIEW Approved
03/14/2019 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change 1. Locate AT&T meter outside of the sight visibility triangle. Please refer to City of Tucson Technical Standards Manual (COT TSM), Section 10-01.5.0 for sight distance requirements.

2. Depict and label the sight triangle per COT TSM Sec. 10-01.5.0 on plan view.

COT TSM can be found at: http://library.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/technicalstandardsmanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

Please contact me at richard.leigh@tucsonaz.gov or 520-837-6647 if you have any questions.

Richard Leigh
Sr. Engineering Associate
Tucson Dept of Transportation
520-837-6647
03/15/2019 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Street Maintenance irrigation does not have any conflicts at this location on the west shoulder.
03/19/2019 LINZUNZA IT_NETWK REVIEW Approved
03/20/2019 JSANDER1 REAL_ESTATE REVIEW Needs Review
03/27/2019 JSANDER1 DOT_ELEC REVIEW Denied This pole will not work.
Sheet A-3: The existing Type-1 streetlight poles that have the luminaire mounted at 40 FT use a 35 FT tall vertical shaft. The arm rises up 5 FT to make the 40 FT height. Here they propose using a pole that has the streetlight arm mounted at 30 FT and an arm that rises up 10 FT to make the 40 FT height.

The only arm available to them is an arm similar to the one used on the Grant Rd installation which resembles the arms we use on the Type 2 A poles, "bent poles" as some people call them. This will not be symmetrical to existing arms.

Sheet S-1 the drawing 1 does not indicate the correct luminaire mounting of 40 FT.

Sheet G-1 N.T.S. 5 (Grounding Details) remove neutral wire and replace with a #12 Black 240 Volt wire. Remove the wire nut and the fuse to indicate a continuous #12 run from the City J-Box (pull box). The HEB-AA fuses will be located in the pull box not in the hand hole.

The drawing on G-1 N.T.S. 5 needs to look like the drawing provided via email to applicant.