Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan Review Detail
Review Status: Completed
Review Details: PREAPPLICATION
Plan Number - T19PRE0104
Review Name: PREAPPLICATION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/11/2019 | ANDREW CONNOR | LANDSCAPE | REVIEW | Completed | 7.6. LANDSCAPING AND SCREENING 7.6.2. APPLICABILITY The provisions of this section apply to the following: A. All new development; and, B. Expansion of existing development, as provided below: 1. Buildings Greater Than 10,000 Square Feet On sites where the gross floor area of the existing building(s) is more than 10,000 square feet, expansion in square footage of land area, floor area, lot coverage, or vehicular use area as follows: a. If the expansion is less than 25%, the standards of this section apply only to the proposed expansion. Existing development on the site is subject to the zoning standards in effect at the time the existing development received zoning approval. b. If the expansion is 25% or greater or if expansions as of February 15, 1991, cumulatively result in a 25% or greater expansion in land area, floor area, lot coverage, or vehicular use area, the standards of this section apply to the entire site. Show compliance with landscaping and screening requirements for the entire site by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-10.0.0, Landscape Plan Requirements. |
| 06/12/2019 | GDAURIA1 | COT NON-DSD | FIRE | Completed | OK with verification of 2hr at existing building. |
| 06/14/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Completed | T19PRE0104 1) Proposed plan shows a lot line running through the new building. The lot line position would have to be adjusted, through a lot combination, so that it does not run through the building 2) Solid Waste. TSM section 8-01.4.0.D. Metal container service will be required when the waste stream calculation exceeds 190 gallons per week. Plans will need to show a trash enclosure for a dumpster and the required service vehicle maneuvering area 3) All curb access ramps, on or around the site, will be updated to PAG standard 207 and be in compliance with ICC A117. Including the use of detectable warnings 4) Water harvesting will be required 5) Pedestrian circulation connection to 13th av is needed John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 06/17/2019 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Completed | OK with verification of 2hr at existing building. |
| 06/17/2019 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Completed | Standard improvements in the right of way will be required. |
| 06/19/2019 | ELISA HAMBLIN | ZONING | REVIEW | Completed | CDRC Thursday Pre-Submittal Transmittal PDSD Zoning Review FROM: Elisa Hamblin, AICP; Principal Planner PROJECT: Thursday Pre-submittal meeting T19PRE0104 Address: 525 W Plata St Parcel(s): 11515110B, 11515110C, 115151080 Zoning: I-1 Existing Use: Commercial Storage, Administrative and Professional Office Proposed Use: Commercial Storage (Expansion) TRANSMITTAL DATE: COMMENTS: 1. Development must comply with the Administrative Manual Section 2-06 - Development Package. 2. The proposal is for an expansion to an existing industrial site which is currently used as a warehouse (commercial storage use). Commercial storage is a permitted use in the I-1 zone and is subject to use-specific standards 4.9.10.A and 4.9.13.Q. 3. The proposed building addition will constitute a 78% expansion to the site. Compliance with current development standards must be demonstrated for the entire site. 4. Required setback along Plata St is 10' as measured from the property line. Setback along 13th Av is 20' or 1.5 times the wall height, as measured from the property line. Setbacks to the south and west are 0'. 5. Commercial storage requires parking at the following standard: 1 space per 5,000 sq. ft. GFA, plus 1 space per 5,000 sq. ft. of outdoor storage area for the first 20,000 sq. ft. of outdoor storage area, plus 1 space per 10,000 sq. ft. of outdoor storage area over 20,000 sq. ft. of outdoor storage area. It appears no outdoor storage is proposed with this site. If not, parking for 26,800 sq ft of GFA would require 5.36 spaces. Parking standards on the proposal appear to meet development standards. 6. At least one sidewalk is required to a project from each street on which the project has frontage. The sidewalk should be located to minimize any conflict with vehicular access to the project. Sidewalks must connect all areas of the development and must also connect to the pedestrian circulation path located along any adjacent street. 7. A lot combination recorded with Pima County will be required prior to any development package approval. 8. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards. If you have any questions please contact me at elisa.hamblin@tucsonaz.gov or (520) 837-4966. |
| 06/28/2019 | AHINES2 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Passed | |
| 06/28/2019 | ALEXANDRA HINES | ZONING-DECISION LETTER | WRITE DECISION LETTER | Completed | Pre-Submittal Complete Notice: T19PRE0104 Project Description: SITE - SILVER STREET WAREHOUSE Prior to submitting, view the meeting review details on www.tucsonaz.gov/pro, search by activity number above. Alexandra Hines, AICP | City of Tucson Planning and Development Services - Lead Planner | 201 N Stone Ave 1st Floor, Tucson, AZ 85701 | (520) 837-6975 - alexandra.hines@tucsonaz.gov |