Plan Number: T19PRE0047
Parcel: Unknown

Address:
3750 S LUNDY AV

Review Status: Completed

Review Details: PREAPPLICATION

Plan Number - T19PRE0047
Review Name: PREAPPLICATION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2019 ANDREW CONNOR LANDSCAPE REVIEW Completed Note: 3750 S LUNDY AV is zoned R-2
Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-10.0.0, Landscape Plan Requirements.
03/19/2019 MASHFOR1 COT NON-DSD FIRE Completed Please indicate existing fire hydrant locations on plan set. Please also provide deferred submittal to TFD for fire sprinklers on this project.
03/20/2019 ELISA HAMBLIN ZONING REVIEW Denied CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Elisa Hamblin, AICP; Principal Planner

PROJECT: Thursday Pre-submittal meeting (T19PRE0047)
Address: 3750 & 37698 S Lundy Av
Parcel(s): 119045900, 119045910
Zoning: C-2, R-2
Existing Use: Vacant
Proposed Use: Multi-Family Residential

TRANSMITTAL DATE: March 20, 2019

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. Proposal 1 calls for a total of six multi-family residential units, two 1-bedroom units on the north (R-2) property and four 2-bedroom units on the south (C-2) property.
a. In the R-2 zone, the setback from multi-family development (a nonresidential use) to nonresidential zones is 10' or 3/4 the height, whichever is greater. The distance between the proposed buildings is shown as 10', but the setback is measured from the zoning boundary.
b. Additionally, in the C-2 zone, the setback from multi-family development (a nonresidential use) to a residential zone is 1 1/2 the height. The distance between the proposed buildings is shown at 10', but the setback is measured from the zoning boundary.
c. Other setbacks appear to be adequate but cannot be fully determined without the proposed building heights.
3. Proposal 2 calls for a total of seven multi-family residential units, three 1-bedroom units on the north (R-2) property and four 2-bedroom units on the south (C-2) property.
a. In the R-2 zone, the setback from multi-family development (a nonresidential use) to nonresidential zones is 10' or 3/4 the height, whichever is greater. The distance between the proposed buildings is shown as 15', but the setback is measured from the zoning boundary.
b. In the R-2 zone, the setback from multi-family development (a nonresidential use) to residential zones is 10' or 3/4 the height, whichever is greater. The proposed setback of 8' to the west does not meet this standard.
c. Additionally, in the C-2 zone, the setback from multi-family development (a nonresidential use) to a residential zone is 1 1/2 the height. The distance between the proposed buildings is shown at 10', but the setback is measured from the zoning boundary.
d. Other setbacks appear to be adequate but cannot be fully determined without the proposed building heights.
e. The proposed parking lot includes a one-way parking area access lane (PAAL) at a 16' width. If these spaces are designed at a 60 degree angle the width may be adequate. But, if this PAAL is required to serve as a fire lane, the minimum width for the PAAL is 20'.
4. Setbacks may be reduced through an administrative review process known as a Design Development Option (DDO).
5. The number of vehicle parking spaces in both proposals appears adequate. Long-term and short-term bicycle parking spaces are required.
6. At least one sidewalk is required to a project from each street on which the project has frontage. The sidewalk should be located to minimize any conflict with vehicular access to the project.
7. In the R-2 zone, multi-family development is subject to use-specific standards 4.9.7.B.6, .9, & .10.
8. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions please contact me at elisa.hamblin@tucsonaz.gov or (520) 837-4966.
03/20/2019 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed Water service requirements for T19PRE0047 3750 South Lundy AV - Site - South Lundy Apartments may be able to be addressed by contacting Hugo Gonzalez at 837-2208 or Ray Munoz at 837-2207 in Tucson Water New Services. Thanks.

Paul Baughman, PE, CFM, Civil Engineer
Tucson Water
310 W Alameda St., Tucson, AZ 85701
520-837-2048
03/25/2019 JOHN VAN WINKLE ENGINEERING REVIEW Completed T19PRE0047

1) Both proposed layouts do not provide sufficient service vehicle maneuvering area per TSM section 8
2) Project is located within a Balanced Basin. Stormwater detention/retention facilities shall be incorporated to ensure that the post development 2,10 and 110 year peak discharges do not exceed pre development conditions
3) A complete onsite pedestrian circulation path along with a connection to Lundy Av will be required. Existing sidewalk along Lundy will need to be confirmed to meet current ADA requirments

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
04/02/2019 ALEXANDRA HINES COT NON-DSD TRAFFIC Passed
04/02/2019 ALEXANDRA HINES ZONING-DECISION LETTER WRITE DECISION LETTER Completed Pre-Submittal Complete Notice: T19PRE0047
Project Description: SITE - SOUTH LUNDY AVENUE APARTMENTS
Prior to submitting, view the meeting review details on www.tucsonaz.gov/pro, search by activity number above.
Alexandra Hines, AICP | City of Tucson Planning and Development Services - Lead Planner | 201 N Stone Ave 1st Floor, Tucson, AZ 85701 | (520) 837-6975 - alexandra.hines@tucsonaz.gov