Plan Review Detail
Review Status: Completed
Review Details: PIA - SUBMITTAL
Plan Number - T19PI00023
Review Name: PIA - SUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2020 | GARY WITTWER | DOT LANDSCAPE | REVIEW | Needs Review | |
| 11/06/2020 | RLEIGH1 | UTILITY CLEARANCES | COT STREETS DIVISION | Needs Review | |
| 11/06/2020 | JIM FEMLING | DOT STREET MAINTENANCE | REVIEW | Reqs Change | |
| 11/06/2020 | RICHARD LEIGH | PIA COORDINATOR | CUSTOMER CALLED; PLANS @ AMBASSSADOR | Completed | |
| 11/06/2020 | ERNIE ENCINAS | DOT_ELEC | REVIEW | Needs Review | |
| 11/06/2020 | RICHARD LEIGH | PIA COORDINATOR | OUT TO CUSTOMER | Completed | |
| 11/06/2020 | RLEIGH1 | UTILITY CLEARANCES | COT WATER NEW DEVELOPMENT | Needs Review | |
| 11/06/2020 | RLEIGH1 | UTILITY CLEARANCES | PC WASTEWATER MGMT | Needs Review | |
| 11/06/2020 | RLEIGH1 | UTILITY CLEARANCES | QUEST COMMUNICATION | Needs Review | |
| 11/06/2020 | RLEIGH1 | UTILITY CLEARANCES | TUCSON ELECTRIC POWER CO | Needs Review | |
| 11/06/2020 | RLEIGH1 | UTILITY CLEARANCES | COX COMMUNICATION | Needs Review | |
| 11/06/2020 | RLEIGH1 | UTILITY CLEARANCES | SOUTHWEST GAS CORP | Needs Review | |
| 11/06/2020 | RLEIGH1 | UTILITY CLEARANCES | EL PASO NATURAL GAS | Needs Review | |
| 11/06/2020 | RLEIGH1 | UTILITY CLEARANCES | KINDER MORGAN ENERGY | Needs Review | |
| 12/10/2019 | ZELIN CANCHOLA | DOT TRAFFIC | REVIEW | Approved | |
| 12/23/2019 | CRAIG SALTZMAN | DOT ENGINEERING | REVIEW | Denied | 1. Add Plan Number I-2019- 040 to all sheets. 2. Add PIA Number T19PI00023 top center of cover sheet with project title. 3. Recorded Sequence number shall be noted on cover sheet of subdivision street improvement plans. Plat must be recorded before submittal of mylars for final review and approval. 4. Please submit utility notification confirmation for the utility companies listed on the PIA utility notification list. The list can be found at: https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Jan14z.pdf 5. Bench Mark information shall refer to City of Tucson Field Book and Page. 6. Include the following paving notes or revise per the following: A) Drainage pipe shall conform to PAG SSPI Section 501or as directed by the engineer. B) Pipe bedding shall conform to PAG Standard Detail 108. C) Aggregate Base Course shall conform to PAG SSPI Section 303. D) Asphaltic Concrete shall conform to COT City Mix. (Indicate Mix Type). F) All concrete shall conform to PAG SSPI Section 1006, Class S, 3,000 PSI compressive strength at 28 days, unless otherwise specified. G) Pavement Section Design documentation, are in accordance to the approved Geotechnical Report, Report Name and Firm Name, Project Number. H) All Drainage Infrastructures, indicated on the plans, are in accordance to the approved Drainage Report approved by Development Services Department. I) Contractor shall obtain all other permits as required by Local, State and Federal requirements. J) Signage and striping should be coordinated with Traffic Engineering and installed at no expense to the public. Call Traffic Engineering at 791-4259 prior to the installation or removal of striping and signage. K) Upon commencement of work, traffic control devices shall be posted and maintained by the contractor until such time as the work is completed. All warning signs barricades etc. shall be in accordance with the manual on uniform traffic control devices adopted by the State of Arizona pursuant to A.R.S. 28-650. Contact Traffic Engineering, (520-791-4259), 48-hours prior to placing or removing any said traffic control devices. L) Contractor shall call Blue Stake as mandated by the Arizona Revised Statutes at 1-800-782-5348 before any construction begins to verify location of existing utilities shown or not shown. Existing utility locations shown hereon are only approximate. It is the contractor's responsibility to confirm horizontal and vertical location of all utilities without damaging same. Damaged utilities shall be repaired at no expense to the City. M) The contractor shall contact and/or coordinate any work with COT Streets & Traffic Maintenance Division, Electric Shop (520-791-3154) prior to relocation or placement of any street lighting or traffic facilities. Contact Gabriel Rascon at (520- 791-3154) for street lighting/traffic signal plan review. N) The contractor shall comply with all applicable Occupational Safety and Health Administration Regulations. O) Floodplain Use Permit No. , has been issued by Development Services Department for work impacting City and FEMA Floodplains. 7. Sht. 3 of 12: Replace Safety Edge Detail with MAG Standard Detail - Pavement Section at Termination 201 Type A for the thickened edge. 8. Sht. 3 of 12: Add Typical Roadway Section for Houghton Road and Old Spanish Trail. 9. Sht. 3 of 12: Add typical section for grader ditch. 10. Sht. 3 of 12: Add Detail for pavement saw cut with limits. 11. Sht. 3 of 12: Add detail for Rip Rap on Houghton Road. 12. Sht. 3 of 12: Add Detail for RCP at station 55+00, include plan and profile. 13. Comply with City of Tucson Drafting Standards. 14. City of Tucson Standard - North arrow Up or to the Right - Stationing increases to the right. 15. Only one plan and profile per sheet. Include stationing along top of profile. 16. Sht. 38of 12: Construction notes: remove note which reads "See Development Packageā¦." PIA Plans shall be a stand-alone set of plans, all information required to build the project shall be included on the plan set. 17. Sht. 8 of 12 all information on Traffic Plan which are required to build the roadway from the plan and profile shall also be included on the plan and profile sheets. 18. Need curve table, include all curves. 19. Sht. 10 of 12: More information is needed to construct grader ditch (station and grades). 20. Sht. 9, 10, 11 and 12 of 12: Continue curb around curves with terminal end sections (PAG Std. Dtl. 209 type 2 curb with 8"reveal. 21. ADA Access Ramps along Collector and Arterial streets shall be PAG Std. Dtl. 207 Type 1. Directing pedestrians to the center of intersections/roadway is no longer acceptable within the city of Tucson on collector and Arterial streets. 22. Profile entrance roads. |