Plan Number: T19PI00001
Parcel: Unknown

Address: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T19PI00001
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2019 GARY WITTWER DOT LANDSCAPE REVIEW Denied Please submit a landscape and irrigation plan for the project.
03/11/2019 ZELIN CANCHOLA COMMENTS COMMENTS Reqs Change March 11, 2019

SUBJECT: T19PI00001 MLK Jr Way

PROJECT REVIEWER: Zelin Canchola,
TDOT Review Section

RESUBMITTAL REQUIRED: DOT Review Section has reviewed the PIA Plan for Traffic Engineering. The proposed plan requires the following change:

Signs:

1. Identify Stop Sign Location at new Road connection to 22nd Street.

2. Add/identify no parking fire access signs (begin and end) along no parking area A/2

3. Add /identify no parking fire access signs (begin and end) along new cul de sac

4. Identify street name signs.


If you have any questions I can be reached at 837-6659 or zelin.canchola@tucsonaz.gov
03/12/2019 CSALTZM1 DOT ENGINEERING REVIEW Denied 1. Use TDOT engineering plan template for this plan set. The latest TDOT engineering plan template can be found at https://www.tucsonaz.gov/tdot/engineering. Please note that the signatory titles should only be provided on cover sheet.
2. Sheet 1of 4: General Note 4: Revise note to indicate the use of TDOT Mix No. 2 for the asphaltic concrete.
3. Sht. 1of 4: Add PIA Number T19PI00001 to cover sheet top center under Title. Remove: "(G-2019__)".
4. Sht. 1of 4: Remove Abbreviations table. Standard abbreviations are included in the PAG 2015 Standard Details.
5. All Sheets add plan number I-2018-022.
6. Sht. 2 of 4: Engineers Notes, note 12 Remove "OPERATORS" and replace with "Contractor".
7. Sht. 3 and 4 need scale for profile.
8. Sht. 3 and 4 need curve tables.
9. Sht. 3 and 4 need Detail of all Access Ramps with grades. Need to be able to check for ADA compliance.
10. Sht. 4 Profile show existing grade beyond Sta. 16+50.74.
11. Sht. 4 Plan E. Seabury CT. Revise to show improvements to remove hammerhead.
03/19/2019 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed Notified EOR that review comments have been posted.
03/19/2019 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
03/19/2019 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed Notified EOR that review comments have been posted.
03/19/2019 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Completed
03/19/2019 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
03/19/2019 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
03/19/2019 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
03/19/2019 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
03/19/2019 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Completed
03/19/2019 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
03/19/2019 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
03/19/2019 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed