Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM09427
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/14/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/14/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide written responses to all plan review comments: 1. SHT G002 Mounting Locations C1; ADA PLUMBING FIXTURE AND ACCESSORIES MOUNTING LOCATION. The measurement of the vertical grab bar from the rear wall to the grab bar location cannot exceed 36" for children use water closets; the distance shown on the detail is 39", please revise. ICC A117.2 Sec. 609.4.2.. 2. SHT G002 PLUMBING FIXTURES. The required number of women's water closets per IBC Sec. 2902.1.1 is 1/65 x #567 = 8.73 (9 total). Per the floor plan on this sheet, the woman's restroom shows 7 w.c.'s and a family assisted restroom for a total of 8 w.c., please revise and provide 9 total w.c.'s for women's restroom. 3. SHT G002 Provide the building classification for WAREHOUSE 120 and the occupant load. The warehouse must be included in the calculations for the maximum allowable area for the building and the occupant load must be factored into the egress calculations. IBC 302.1; IBC 1004.1. 4. SHT G002 On this text box, please provide the calculations for the allowable area increase due to frontage. IBC Sec. 506.3.2. 5. SHT G002 The egress plan should contain a graphic representation of the routes and measurements for the Common Path of Egress Travel and the Exit Access Travel Distance. Exit access travel distance shall be measured from the most remote point of each room, area or space along the natural and unobstructed path of horizontal and vertical egress travel to the entrance to an exit. IBC 1017.1, 1017.3. 6. SHT G002 Please provide a UL detail or reference to IBC TABLE 721.1(2) RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS for the existing 2-hr. rated 8" CMU walls between the project tenant space and the attached buildings. IBC 721.1. 7. SHT S1.0 Provide structural calculations for the work shown on the structural sheets. Specify design loads and other information pertinent to the structural design and details. IBC 1603.1. 8. SHT S1.0 Submit general structural notes for the structural design work. IBC 1603.1. 9. SHT S1.0 Submit structural reinforcing plans, calculations and drawings for the new pool construction. IBC 1603.1. 10. SHT G002 Saunas and steam rooms are required to be accessible; Where saunas or steam rooms are clustered at a single location, at least 5 percent of the saunas and steam rooms, but not less than one, of each type in each cluster shall be accessible. IBC 1109.6. 11. SHT G002 Note on plans: Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space, for the intended configurations. IBC 1004.9. 12. SHT G002 Please provide a description of the space that occupants exit into from the KIDS CLUB ACTIVITY AREA. IBC 107.2.1. 13. SHT A603 Specify type of fasteners for attachment of walls/partitions to the roof-ceiling and slab; provide ICC Report for fasteners. IBC 107.2.1 14. SHT A402 Specify slope of egress ramp for ADA purposes and edge protection at guardrail; indicate spacing of intermediate railing for required guards at elevated walkways. ICC A117.1, IBC 1015.2. 15. SHT A611 Specify room ceiling and wall finish description throughout, especially because steam room, sauna and pool are being constructed. IBC 107.2.1. 16. SHT A602 Complete the ROOM FINISH SCHEDULE table. IBC 107.2.1. SHT A602 Provide a HARDWARE SCHEDULE; identify panic and exit hardware doors on doors on the door schedule. IBC 1010.1.10. 17. SHT A101 Toilet rooms located in child day care facilities and containing two or more water closets shall be permitted to have one water closet without an enclosing compartment, other water closets are required to have a separate compartment with partitions and door. The GIRLS restroom is required to have a separate compartment for 1 water closet. IBC 1209.3.1 18. SHT A103 Where dressing rooms or locker rooms are provided, at least 5 percent, but not less than one, of each type of use in each cluster provided shall be accessible; please identify. IBC 1109.12.1. End of building comments. |
| 01/22/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 2. Coordinate the disposal of the HVAC condensate with the plumbing plan. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. 3. Provide the total outside air flow rate for the pool dehumidification unit on the equipment schedule. Reference: Section 107.2.1, IBC 2018. 4. Coordinate the zone ventilation calculations with the scheduled outside air balancing date for each rooftop AC unit. Reference: Section 107.2.1, IBC 2018. 5. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems moving than 2,000 CFM and capable of spreading smoke to multiple rooms. Reference: Section 606.2.1, IMC 2018, as amended by the City of Tucson. |
| 01/22/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Water heaters with inputs of 200,000 BTUH or greater are classified as boilers and require approval from the Arizona Boiler inspector. Reference: Title 20, Chapter 5, Article 4, Arizona Administrative Code. 2. Verify that all of the gas loads have been accounted for in the gas load calculations table on sheet P001. Reference: Section 402.2, IFGC 2018. 3. Verify the size of the gas pipe downstream of RTU-3, 850 MBH at 400 feet requires a 1-1/4" pipe based on Table 402.4 (5), IFGC 2018. 4. What is a WCB (on sheet P301); is it the WMB (on sheet P002)? If so where is the lint trap (LT-1)? Reference: Section 107.2.1, IBC 2018 5. Verify that the metering faucets for the public lavatories will operate for at least 10-seconds and will deliver no more than 0.25 gallons per cycle. Reference: Section 606.4, ICC/ANSI A117.1-09. 6. An approved two-way cleanout fitting is a listed single fitting, not field-assembled as shown on sheet P401. Reference: Sections 707.1 (3), 708.1.3, and 708.1.8, IPC 2018. 7. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (e.g. floor and trench drains). Reference: Section 905.4, IPC 2018. |
| 01/22/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 01/22/2020 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T19CM09427 / Chuze Fitness Center (Previous Use - Retail) Tenant Improvement / ADA Parking Restriping (1st Review) 6363 E 22nd Street - C-1 and C-2 Zoning TRANSMITTAL DATE: January 22, 2020 DUE DATE: January 30, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Revise the vicinity map on the cover sheet to depict the correct location of this project location. 02. COMMENT: The ADA parking striping has been revised. The two ADA spaces on the south end of the west parking spaces have not been provided with an access aisle. An access aisle is required adjacent to the passenger side of the two spaces. Revise the string plan as required. (Sheet AS101) If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 01/22/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. A 2-1/2" water meter is not available from Tucson Water. A 2" water meter is allowed to service up to 120 GPM according to Tucson Water and it is currently installed to serve this building. Contact Ray Muñoz at Tucson Water (520-837-2207) for further information. 2. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 01/30/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E301. Correlate the rating in amps for the OCPD for panel HB, between the Power Riser Diagram and the panel schedule for "MDP". The line diagram shows 400 amps and the panel schedule shows 600 amps. 2. Ref; Plan Sheet E 402. Please itemize the lumen calcs further to show the totals in lumens for each type of exterior luminaire. Is the value of 419,439 total proposed lumens/ How was that computed? 3. Show the option used as well as the lighting area. Table 401.1. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/29/2020 | AMARTIN1 | REJECT SHELF | Completed |