Permit Number: T19CM09426
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM09426
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Completed
02/04/2020 ROBERT SHERRY WATER REVIEW Completed
02/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Detail 3/P200 calls for the installation of a vacuum breaker: a vacuum relief valve is required. [Initial comment: Install the proposed vacuum relief valve for the water heater per the manufacturer's listing information, i.e. on the cold water inlet to the water heater. Reference: Section 303.2, IPC 2018.]
2. Revise details 2/P100 and 4/P100 to show the recirculation system installed per the manufacturer's installation instructions. The recirculation loop itself forms the source of the hot water. The ½" hot water branch from the recirculation loop to the stop valve for the lavatory cannot exceed 2-feet in length. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
02/04/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/06/2020 SBORZAK1 REJECT SHELF Completed
02/04/2020 SBORZAK1 OUT TO CUSTOMER Completed