Permit Number: T19CM09426
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM09426
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2020 MARTIN BROWN FIRE REVIEW Approved
01/10/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/10/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A030; Egress Plan: At each exit door, please indicate the actual number of occupants that will exit at that location per the IBC Section 1004.
2. Sheet A030; Egress Plan: Per the IBC Section 1010.1.2.1, doors shall swing in the direction of egress travel for 50 or more occupants. Please verify the double door exit meets that requirement.
3. Sheet A300; Reflected Ceiling Plan: At the double door exit into the mall common area, is an exit sign/emergency light required per the IBC Section 1013? Please verify.
4. Sheet S-002; Instructions: Item 1 indicates the 2006 IBC. Please revise all references to the 2006 code on all sheets.
5. General: Please provide structural calculations for the new storefront framing.
6. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
01/17/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Section 6.4.2.1, ASHRAE 90.1-2016.
2. The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2018 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2018; for HVAC systems serving multiple zones (e.g. RTU-2), see Section 403.3.1.1.2.3, IMC 2018.
3. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
01/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
3. Install the proposed vacuum relief valve for the water heater per the manufacturer's listing information, i.e. on the cold water inlet to the water heater. Reference: Section 303.2, IPC 2018.
4. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
01/17/2020 IMONSHI1 ENGINEERING REVIEW Passed
01/17/2020 IMONSHI1 ZONING REVIEW Approved
01/17/2020 ROBERT SHERRY WATER REVIEW Completed
01/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide compliance with ASHRAE 90.1, 8.4.2 for automatic receptacle control.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2020 SBORZAK1 REJECT SHELF Completed