Permit Number: T19CM09408
Parcel: 11103077A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM09408
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2020 MARTIN BROWN FIRE REVIEW Approved
01/15/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Plans that are not 'FOR REFERENCE ONLY' require the seal of a professional registrant.
2. The reference plans and equipment specifications are not legible, please provide clear copies of all specifications.
01/15/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Building permits for modifying the partition wall to a load bearing wall as described in the structural analysis, were not found for this address. Before the permit for the solar installation can be approved, the wall modification will need to be permitted and inspected. GP

Final Status

Task End Date Reviewer's Name Type of Review Description
03/05/2021 KROBLES1 REJECT SHELF Completed