Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM09398
Parcel: 13216600A

Address:
4004 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM09398
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2020 MARTIN BROWN FIRE REVIEW Approved
01/08/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/15/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.2; Code Analysis Narrative (Chapter 10): The Exit Distance references Table 1017.1. Please revise that reference per the 2018 IBC.
2. Sheet A0.2; Code Analysis Narrative (Chapter 10): Please add a note reference to the IBC Table 1006.2.1 for the maximum common path of egress travel distance (100').
3. Sheet A0.2; Governing Regulations (Chapter 11): Since this is a government building, please reference the 2010 ADA Standards in the Governing Regulations, and remove the 2009 ICC/ANSI.
4. Sheet A0.2; Governing Regulations (Chapter 11): Please add a reference to the 2010 ADA Standards for the parallel approach to a sink (Section 606).
5. Sheet A0.2; Governing Regulations (Chapter 11): Please add a reference to the 2010 ADA Standards for accessibility signage (Chapter 7).
6. Sheet A0.2; Governing Regulations (Chapter 12): A note indicates floor tile in bathing rooms and toilets shall extend 6" minimum up the wall per Section 1209.2.1. Revise that to 4" per Section 1209.2.1. Please verify.
7. Sheet A2.0 (Floor Plan); Sheet A4.0 (Section 1): The Grid Line on Section 1 indicates B on the left side of the section, while the Floor Plan indicates A. Please coordinate.
8. Sheet A2.0; Floor Plan: Please cut Section 3/A4.0 on the Floor Plan.
9. Sheet A2.1; Floor Plan 1: Please indicate on this Floor Plan the area location for the Enlarged Plan 2/A2.1.
10. Sheet A2.1; Floor Plan 1: Please indicate horizontal grid lines on the Floor Plan.
11. Sheet S1.0; Detail 05: Please indicate the length of the 1/2" diameter expansion anchors.
12. Sheet S1.0; Detail 01: Please provide structural calculations for the light pole caisson design.
13. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
01/17/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2018.
01/17/2020 ROBERT SHERRY WATER REVIEW Completed
01/23/2020 DJELLEN1 ZONING REVIEW Approved
01/28/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E0.3. Where are the 'F8' and 'K2' exterior luminaires. Could not locate.
#2. Ref; Plan sheet E5.0.
(a) Indicate conduit and conductor sizes and types for the secondary feeders from the utility transformer to SES #1.
(b) Provide for GFI protection at the service and downstream equipment as required per NEC 230.95, and 240.13.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
01/31/2020 JOHN VAN WINKLE ENGINEERING REVIEW Approved