Permit Number: T19CM09396
Parcel: 99999999M

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM09396
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets SG501 through SG503; Details: The details reference the Post/Ballast Schedule (for post size), the X-Bracing Schedule, and the Bay Schedule (for top chord and purlin size). Please verify that the sizes of all referenced members are indicated on the drawings (in details or notes) for inspection purposes.
2. Structural Calculations; Page 2: The Design Criteria indicates the 2012 IBC for the design guidelines. Tucson is currently under the 2018 IBC. Please revise this note and verify all structural calculations are adequate under the 2018 code.
3. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov.
01/15/2020 MARTIN BROWN FIRE REVIEW Approved
01/16/2020 DJELLEN1 ZONING REVIEW Approved
01/24/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2020 SBORZAK1 REJECT SHELF Completed