Permit Number: T19CM09370
Parcel: 11016074A

Address:
6095 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM09370
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved
01/02/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/02/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Coordinate the waste and vent diagram with the plumbing plan. A 4" building drain requires a 4" cleanout. [Initial comment: Clarify the arrangement of the fixture drains (i.e. provide a waste and vent diagram).]
2. The horizontal drains from P4, P3, and P1H cannot connect to the vent for P2H. [Initial comment: A common vent can accommodate only two fixtures.]