Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM09370
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2019 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 12/20/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the exhaust for the restroom. |
| 12/20/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete electrical plans for lighting and power. Show all receptacles and lighting being removed, relocated, or new. See Electrical Requirements in the City of Tucson Commercial Plan Submittal Requirements. Can be printed or downloaded from www.tucsonaz.gov/pdsd. 2. Provide compliance with the 2018 IECC for the lighting. Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
| 12/20/2019 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
| 12/20/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/20/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/20/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the arrangement of the fixture drains (i.e. provide a waste and vent diagram). 2. Clarify the fixture tags (e.g. where is P-4) and the keynotes (e.g. why does keynote P1 point to waste and vent piping?) 3. A common vent can accommodate only two fixtures. 4. Provide tepid water to the lavatory with a mixing valve listed to ASSE 1070. 5. Show that the distance from the hot water source to the lavatory is no longer than 2-feet. Reference: Section C404.5, IECC 2018. |
| 12/20/2019 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/20/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |