Permit Number: T19CM09370
Parcel: 11016074A

Address:
6095 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM09370
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2019 IMONSHI1 ZONING REVIEW Approved
12/20/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the exhaust for the restroom.
12/20/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete electrical plans for lighting and power. Show all receptacles and lighting being removed, relocated, or new. See Electrical Requirements in the City of Tucson Commercial Plan Submittal Requirements. Can be printed or downloaded from www.tucsonaz.gov/pdsd.
2. Provide compliance with the 2018 IECC for the lighting.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements.
12/20/2019 IMONSHI1 ENGINEERING REVIEW Passed
12/20/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
12/20/2019 ROBERT SHERRY WATER REVIEW Completed
12/20/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the arrangement of the fixture drains (i.e. provide a waste and vent diagram).
2. Clarify the fixture tags (e.g. where is P-4) and the keynotes (e.g. why does keynote P1 point to waste and vent piping?)
3. A common vent can accommodate only two fixtures.
4. Provide tepid water to the lavatory with a mixing valve listed to ASSE 1070.
5. Show that the distance from the hot water source to the lavatory is no longer than 2-feet. Reference: Section C404.5, IECC 2018.
12/20/2019 JPEELDA1 FIRE REVIEW Approved
12/20/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed