Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM09299
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/19/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/19/2019 | SMEGGIS1 | ENGINEERING | REVIEW | Passed | |
| 12/19/2019 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete electrical plans for power and lighting. Also compliance with the 2018 IECC and the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
| 12/19/2019 | ENEWCOM1 | FIRE | REVIEW | Reqs Change | Indicate on plans how IFC section 503, fire department access, will be addressed. |
| 12/19/2019 | SARAH MEGGISON | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/19/2020 | PMARTIN1 | OUT TO CUSTOMER | Completed |