Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM09270
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Delete the obsolete plumbing plan on sheet A1.0 |
| 01/08/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the termination of the two new exhaust ducts. 2.Provide electrical service to the exhaust fans. 3. Delete General Note #6 on sheet A1.0 that states that there are no mechanical changes to the suite. |