Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM09266
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/15/2020 | AMARTIN1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
12/18/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 2. Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucso 3. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3, IMC 2018 |
12/18/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide load calcs for panel 'X1' and a complete panel schedule. Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
12/18/2019 | MRESS1 | ENGINEERING | REVIEW | Passed | |
12/18/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/18/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/18/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
12/18/2019 | MROSS2 | FIRE | REVIEW | Approved | |
12/18/2019 | MALLORY RESS | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/15/2020 | AMARTIN1 | OUT TO CUSTOMER | Completed |