Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T19CM09261
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/13/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Coordinate the size of the water meter, backflow preventer, and water service pipe to the building with the architectural site plan, ASP.1. Reference: Section 107.2.1, IBC 2018. 2. Revise the connection of the building drain to the private sewer collection system as shown on sheet ASP.1; the private sewer collection system flows from west to east. Reference: Section 706.3, IPC 2018. 3. The scupper size calculation on sheet A2 appears to be incorrect. A projected area of 3328 square feet yields a flow rate of 103 GPM which requires a vertical pipe size of 4" based on Table 1106.2, IPC 2018. Per Section 1106.5, IPC 2018, the scupper size (width) is equal to the circumference of the vertical pipe size determined using Table 1106.2, IPC 2018 which is 12.6". |
| 01/13/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Coordinate the building component descriptions in the COMcheck Envelope Compliance document with the architectural drawings (e.g. the building sections call for R-21 cavity insulation in the exterior walls but COMcheck shows R-19 cavity insulation in the wall descriptions). |
| 01/13/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/14/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/21/2020 | MALLORY RESS | ZONING | REVIEW | Reqs Change | FROM: Mallory Ress, Planner PDSD Zoning Review Section PROJECT: T19CM09261 Shell Building (1st Review) 2121 N Craycroft Rd TRANSMITTAL DATE: January 21, 2020 DUE DATE: January 21, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has reviewed the plans for compliance with the last approved Development Package (DP) for the subject property, DP17-0182. The review is also subject to rezoning C9-16-16. 02. COMMENT: Site plan shown does not match approved DP17-082 specifically in regard to Keynote 18 and location of short term bicycle parking as well as the sidewalk/accessible curb ramp depicted in the same location. The orientation of the sidewalk/accessible curb ramp depicted in keynote 19 appear to cause a reduction in the parking located to the west of the shell building. If changes to the site plan are proposed, a revised DP will need to be submitted, reviewed and issued prior to approval of this application. If these changes are in error applicant should match the site plan to the approved DP and stamp site plan "for reference only". 03. COMMENT: Change note 2.B. under Code Study - 2018 International Building Code to correctly state the height requirements for this project, which is a max of 20'. 04. COMMENT: Sheet 6, Elevations need to be corrected to show the flat roof height of the building, not just the top of parapet. The allowable height of building 7 is 20' with parapets allowed up to 4' above the roof of the structure. 05. COMMENT: Ensure that rezoning conditions regarding visual appealing design elements are met the south façade of the shell building; "All walls visible from a public right of way and/or adjacent to existing residential development, are to be graffiti-resistant and incorporate one (1) or more visually appealing design treatments, such as the use of two (2) or more decorative materials like stucco, tile, stone, or brick; a visually interesting design on the wall surface; varied wall alignments, (jog, curve, notch, setback, etc.); and/or trees and shrubs in voids created by the wall variations." Clarify that a graffiti resistant material is being utilized. 06. COMMENT: If any changes are necessary, due to the PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning. 07. COMMENT: Once the plans have been reviewed and approved by the Commercial Plan Reviewers and zoning has verified consistency with the PDSD approved and signed copy of the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, Contact Mallory Ress at (520) 837-6933 or by email Mallory.Ress@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 01/23/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | T19CM09261 1) The site plan in the building plan, sheet ASP.1 does not match the site plan found in the approved development package. Update as needed 2) Ensure that roof drains, from the new building, scupper underneath sidewalks as needed. Reference COT Technical Standards Manual (TSM) section 7-01.4.1.e. Coordinate with the Development Package John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 12/26/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 12/27/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/13/2020 | KROBLES1 | REJECT SHELF | Completed |