Permit Number: T19CM09250
Parcel: 126210940

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM09250
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2020 MROSS2 FIRE REVIEW Reqs Change With the additions, the house will have a fire flow requirement (water available from nearest hydrant) of 2500 GPM. As most residential water systems are designed to supply 1000 GPM, it is highly unlikely this much water will be available. Check with Richard Herran at Tucson Water and see if the system can supply 2500 GPM @ 20 psi. If the system can support this requirement, provide documentation.
If it cannot, a residential fire sprinkler system will be required.
12/20/2019 IMONSHI1 ZONING REVIEW Approved
12/31/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T19CM09250
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLUMBING PLANS:

1. Show a gray water collection tank with an overflow connection to the black water line, and include a backflow valve on the water meter connection. Show an electrical circuit for a system pump.
2. Show horizontal (GRAY WATER) branch drain pipes sized with acceptable number of fixture units, Table P3005.4.1. (max 6 units on 2" pipe size)

MECHANICAL PLANS:

1. Provide (an HVAC system with) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1507.3. Show the system and flow rate on the plans.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Deferred calculations must be approved through revision process prior to mechanical inspections.

ELECTRICAL PLANS:

1. Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.