Permit Number: T19CM09244
Parcel: 11812050A

Address:
248 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM09244
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the installation of the grease duct. The mechanical plans call for prefabricated double-wall exhaust duct but the architectural plans call for field-fabricated steel duct with 3M Firemaster ductwrap.
12/30/2019 ROBERT SHERRY WATER REVIEW Completed
12/30/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the size of the existing water meter serving this address. Tucson Water records show that meter number 1548924 is a 5/8" meter. Calculate the total water demand served by this meter and determine if the meter is adequate to meet the demand.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2020 PMARTIN1 APPROVAL SHELF Completed
01/17/2020 PMARTIN1 OUT TO CUSTOMER Completed
01/17/2020 PMARTIN1 REJECT SHELF Completed