Permit Number: T19CM09185
Parcel: 11504393A

Address:
1128 N 2ND AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM09185
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
10/22/2020 JPEELDA1 FIRE REVIEW Reqs Change We would also need to know the type of constuction to advise you of the required fire flow if you do not have access to a IFC please contact me at Jennifer.Peel-Davis@Tucsonaz.gov
Tucson water shows that if it s required over 1,500 gpm than a sprinkler system would be required. Depending on the type of construction you might need 1,750 gpm therefore you would need to add fire sprinklers and that shall be noted on your drawings.
Plans shall also have a code annalysis area