Permit Review Detail
Review Status: Active
Review Details: REVISION - - 1ST
Permit Number - T19CM09168
Review Name: REVISION - - 1ST
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed | |
| 05/28/2020 | ELISA HAMBLIN | ZONING | REVIEW | Approved | ZONING REVIEW TRANSMITTAL FROM: Elisa Hamblin, AICP Principal Planner PROJECT: Permit #T19CM09168 6113 S Avenida Dunas New SFR TRANSMITTAL: May 6, 2020 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). The proposed single-family residence has a wall height of 9’7 1/8” from the design grade to the top of wall on the western façade. The required setback would be 6’5”. The proposed setbacks range from 5’10” to 6’1”. A DDO is required. |
| 05/28/2020 | ELISA HAMBLIN | ZONING | REVIEW | Approved | DDO has been approved and plan is now approvable. See DDO-20-29 (T20SA00141). |