Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM09159
Parcel: 12902091E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM09159
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2020 IMONSHI1 ZONING REVIEW Needs Review
01/22/2020 IMONSHI1 ENGINEERING REVIEW Passed
01/22/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/17/2019 MARTIN BROWN FIRE REVIEW Approved
12/17/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Passed
12/17/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/19/2019 ROBERT SHERRY WATER REVIEW Completed