Permit Number: T19CM09148
Parcel: 132191240

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM09148
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

There was no written response located in this re-submittal as requested per the previous review comments.

The resubmittal was insufficient to determine full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. Ordinance # 10963.

Please update the lighting plans with the following information on the plans as required per section 104 (plan submittal requirements);

Revise the Outdoor Lighting Calculations to show the lighting area and correct option. See Table 401.1. The 400,000 shown in the lumen calculations is not correct. No such value possible. Be advised that the luminaires shown for this project are LED type, not LPS (LOW PRESSURE SODIUM)

Total lumens allowed per table 401.1 vs total final lumens including existing lighting on the property. Existing luminaires on this parcel must be included in the lumen calculations.

Luminaire schedule must correlate with luminaires shown on the site lighting plan.

Indicate light source color temperature output and shielding for all exterior luminaires including under canopy .

Provide luminaire manufacture cut sheets with the luminaire specified.

Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

Specify any exceptions used.

Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2018 IBC 107.2.1, 2017 NEC, Tucson/Pima County Outdoor Lighting Code. City of Tucson Commercial Plan Submittal Requirements.