Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM09148
Parcel: 132191240

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM09148
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Provide more detail to verify compliance with the Outdoor Lighting Code.
1. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.
2. Provide lighting plans with the following information on the plans;

(a) Size of the parcel in acres.
(b) See table 401.1, lighting area and option and indicate this information in the lighting site plan.
(d) 402.1 (light source color temperature requirements), shielding requirements, etc .
(e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.
(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.
(g) Specify any exceptions used.
(h) Curfew lighting controls If applicable.
Do not confuse the Outdoor Lighting Code with the IECC.
Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.